0 Cookie Img

HSD Detector

HSD Detector
HSD Detector
Product Code : KD-14
Product Description

HSD Detector (KD-14)

Thin and compact designed detector

  • Easy to replace unit type gas sensor.
  • Water and dust proof structure (Degree of Protection: IP65)
  • Approvals: Ex d IIC T5
  • Early detection of hydrogen leakage near the ceiling is possible with thin design.
  • Compact designed diffusion type gas detector
Specifications:

Model

KD- 14A

KD- 14B

Sampling Method

Diffusion type

Detection Principle

Hot wire semiconductor

Catalytic combustion

Target Gas

Hydrogen

Detection Range

0-2000 ppm

0-100% LEL

Explosion-proof

Ex d IIC T5

Degree of Protection

IP65

Applicable Cable

Cable diameter: 10-13mm
4-core shield cable: CVV-S 0.75 mm2
1.25 mm2 or 2.0 mm2

Operating Temperature and Humidity

Temperature: -10 to 50 degrees C
Humidity: 10 to 90% RH (0-50 degrees C)

Power supply

Supplied by indicator unit

Dimensions

W 158 x H 158 x D 68mm

Weight

Approx. 1.2kg



Contact Us

108-109, Chiranjiv Tower, 43, Nehru Place, New Delhi, Delhi, 110019, India